PUE and how much power data centers use

PUE, power usage effectiveness, is a data center's total energy divided by the energy its IT equipment uses, measured over a year. A PUE of 1.0 would mean every kilowatt-hour goes to computing; the industry average was 1.52 in Uptime Institute's 2026 survey, while Google reports 1.09 across its fleet. US data centers used 176 TWh in 2023, about 4.4% of the country's electricity, and could reach 6.7% to 12% by 2028. This guide explains the metric, the benchmarks and the numbers behind data center power use.

Published November 20, 2026.

What PUE is

Power usage effectiveness compares everything a data center draws with what reaches the computers. The rest goes to cooling, power conversion losses, lighting and other overhead. The Green Grid published the metric in 2007 and it is now the international standard ISO/IEC 30134-2. Its inverse, DCiE, expresses the same thing as a percentage.

How to calculate PUE

  • PUE = total facility energy ÷ IT equipment energy, both in kWh over a full year.
  • Example: a site uses 10,000 MWh in a year and its IT equipment uses 8,000 MWh. PUE = 10,000 ÷ 8,000 = 1.25, so each kWh of computing carries 0.25 kWh of overhead. DCiE = 80%.
  • Where you measure matters: at the UPS output (level 1), the PDU output (level 2) or the IT equipment itself (level 3, at least every 15 minutes).

Industry average PUE

YearAverage PUE (Uptime Institute)
20072.50
20111.98
20141.65
20181.58
20201.59
20221.55
20241.56
20251.54
20261.52

Uptime describes seven years of near standstill: older sites dominate the average, while respondents' largest sites averaged about 1.45 in 2026. Average rack density rose above 11 kW in 2026, and 24% of respondents now run racks of 30 kW or more.

PUE at Google, Meta, Microsoft and AWS

OperatorPUEYear
Google (fleet)1.092025
Meta1.082024
AWS (global)1.142025
Microsoft (fleet)1.17FY2025

Hyperscalers reach these figures with large, purpose-built sites, outside-air and liquid cooling, and high utilization. Liquid-cooled AI racks change the picture again: see liquid cooling and GPU power and cooling.

How much power data centers use

MeasureFigureSource
US data centers, 201458 TWhDOE / LBNL
US data centers, 2023176 TWh, about 4.4% of US electricityDOE / LBNL
US data centers, 2028 projection325–580 TWh, 6.7–12%DOE / LBNL
World, 2024About 415 TWh, about 1.5% of electricityIEA
World, 2025About 485 TWh (+17%)IEA
World, 2030 projectionAbout 950 TWh, about 3%IEA

The IEA attributes 45% of 2024 data center use to the US, 25% to China and 15% to Europe, and says AI-focused data centers' use grew 50% in 2025.

How big a data center is

TypeTypical power
Enterprise colocation requirement500 kW–3 MW per user (JLL)
Conventional data center10–25 MW (IEA)
Hyperscale or AI data center100 MW or more (IEA)
Largest campuses under constructionAbout 2 GW (IEA)

See the largest data centers in the world, and what it costs to build one in data center cost per MW.

WUE: the water metric

Water usage effectiveness is the liters of water used for cooling and humidification per kWh of IT energy. Reported figures: AWS 0.12, Meta 0.19 and Microsoft 0.27 L/kWh. Closed-loop liquid cooling, as at Microsoft's Fairwater sites, avoids evaporating water.

Power producers, cooling vendors and operators meet at Intelligence Disrupt 2027 in Dallas, March 22–24.

Questions

What is PUE?
Total facility energy divided by IT equipment energy over a year. The Green Grid introduced it in 2007, and it is standardized as ISO/IEC 30134-2.
What is a good PUE?
1.0 is the theoretical ideal. The industry average was 1.52 in 2026 according to Uptime Institute, large sites averaged about 1.45, and the hyperscalers report 1.08 to 1.17.
How do you calculate PUE?
Divide the facility's total annual energy by the IT equipment's annual energy. A site that uses 10,000 MWh while its IT uses 8,000 MWh has a PUE of 1.25.
What PUE does Google have?
Google reports a fleet-wide trailing twelve-month PUE of 1.09 for 2025 and the second quarter of 2026.
How much electricity do US data centers use?
176 TWh in 2023, about 4.4% of US electricity, according to Lawrence Berkeley National Laboratory, which projects 325 to 580 TWh, 6.7% to 12%, by 2028.
How much electricity do data centers use worldwide?
About 415 TWh in 2024 and about 485 TWh in 2025, according to the IEA, which projects about 950 TWh by 2030, around 3% of global electricity demand.
How much power does one data center use?
Conventional data centers run 10 to 25 MW, hyperscale and AI data centers 100 MW or more, and the largest campuses under construction about 2 GW, according to the IEA.
What is WUE?
Water usage effectiveness: liters of water used for cooling per kWh of IT energy. AWS reports 0.12, Meta 0.19 and Microsoft 0.27.

More guides

Sources

  1. The Green Grid, PUE: a comprehensive examination of the metric (WP49) · 2012
  2. ISO/IEC 30134-2, Power usage effectiveness · 2016
  3. Uptime Institute, Global Data Center Survey 2025 · 2025-07
  4. Uptime Institute, Global Data Center Survey 2026 · 2026-07
  5. Google, data center efficiency · 2026
  6. Meta, 2025 Environmental Data Index · 2025
  7. Microsoft, datacenter efficiency · 2026-03-10
  8. Amazon, AWS cloud sustainability · 2026
  9. US DOE, LBNL data center energy report · 2024-12-20
  10. IEA, Energy and AI · 2025
  11. IEA, Key questions on energy and AI · 2026